Room Transmission Heat Loss with Fixed Opening Sizes
Estimate a room’s simplified transmission heat loss using wall U-value, captured window and door assumptions, and indoor/outdoor temperatures.
- Formula & worked example
- Private in your browser
- No signup
Calculator inputs
Loading calculator…
How to use this calculator
- Enter the known values in the units shown. Results update as you type.
- Where results are editable, change one to solve backwards. Lock a value to hold it fixed.
- Use the worked example to check the method. Reset restores the starting fields.
Private by default
Inputs and results stay in this browser tab. Bookify does not upload or store the values you enter.
Formula and method
For a 5 m by 5 m room, 2.7 m high, with four external walls, no openings and wall U-value 1 W/(m²·K), a 40 °C temperature difference gives 2160 W of modeled wall heat loss.
Transmission power = modeled heat-loss coefficient × (indoor temperature − outdoor temperature)
Worked example
Enter these known values and leave the other values blank.
- Length
- 5 m
- Width
- 5 m
- Height
- 2.7 m
- Number of external walls
- 4
- Insulation
- Preset wall U-value: 1 W/(m²·K)
- Level
- Intermediate level
- Window count (1.08 m² each)
- 0
- Door count (1.8 m² each)
- 0
- Internal
- 20 °C
- Ambient
- -20 °C
- Wall U-value
- 1 W/(K⋅m²)
- Modeled heat-loss coefficient
- 54 W/K
- Transmission heating power only
- 2160 W
Assumptions and limitations
- External wall area is the full room perimeter times height times external-wall count divided by four. This equal-share approximation cannot identify which long or short walls are exposed in a non-square room.
- Every window is fixed at 1.08 m² with U-value 2.5 W/(m²·K); every door is 1.8 m² with U-value 2.4 W/(m²·K). Total opening area cannot exceed modeled external-wall area.
- The captured floor-level coefficient adds floor area times 1 W/(m²·K) for ground floor, 0.7 for top floor, and zero for intermediate floors. These are fixed assumptions, not measured construction properties.
- The model omits ventilation, air leakage, thermal bridges, warm-up demand, solar gains and equipment efficiency. It estimates transmission only and does not provide a complete heating-system size.
- Indoor temperature must be at least outdoor temperature for this heating estimate. Equal temperatures give zero transmission power.
Common questions
Can I use the preset insulation labels as measured U-values?
No. The choices are fixed illustrative coefficients. Enter a verified assembly U-value in custom mode when one is available; the opening and floor assumptions still remain fixed.
References
Bookify permits zero heat flow at equal temperatures, rejects negative heating demand and prevents fixed-size openings from exceeding the modeled wall area. Mechanical horsepower uses exactly 550 foot-pounds-force per second instead of a rounded factor. The power unit uses the International Table BTU per hour consistently with the reviewed energy convention.
Related calculators
Explore home and garden calculators 🏡 or browse all construction calculators.